CT-2012 4-20 mA Control/Alarm/Indicator
4-20 mA Control/Alarm/Indicator
Model : CT-2012 ISO-9001, CE, IEC1010
FEATURES
* Input : 4-20 mA DC, linear. |
* User can default the desired display value between -1999 to 9999 ( decimal point can be selected to DP1, DP2, DP3 ) and all the preset data will be saved into the memory circuit permanently. |
* According the 4 to 20 mA input signal, user can preset the desire display value between -1999 to 9999 ( decimal point can select to DP1, DP2, DP3 ). Until set the display value, all the data will save into the memory circuit permanently |
* When CT-2012 cooperate LUTRON's 4 to 20 mA transmitters ( or any other transmitters if it build 4 to 20 mA output signal ), whole system will become the high performance Controller/Alarm/Indicator for following measuring functions : Humidity, Light, pH, Dissolved Oxygen, Conductivity, Vibration, Pressure, Sound, Temperature, RPM, Hz, Load cell ( Weight, Force ), Potential ( Angle, Level ). ACV, ACA, DCV, DCA, WATT.... |
* Easy to adjust the function factors by push button on the front panel. |
* Control output : 2 points ( COM, NO ). |
* Alarm output : 2 points ( COM, NO ). |
* Control Relay will make action when the reading value reach to control value. |
* Hysteresis value setting for control and alarm function. |
* Large red LED display, high brightness and easy to read. |
* Microprocessor circuit ensures high accuracy and provides special functions and features. |
* DC 24V power supply output. |
* RS232/USB computer interface. |
* Power : 90 ACV - 264 ACV, 50/60 Hz. |
* Standard 96 X 48 mm DIN case. |
* Optional data acquisition software. |
GENERAL SPECIFICATIONS
Display | * 4 digits red LED, 14 mm ( 0.55 inch ) digit height | |
* 4 indicators : PV ( process value ) indicator SV ( set value ) indicator Control out indicator Alarm out indicator | ||
* According the 4-20 mA input signal, user can preset the desire display value between -1999 to 9999 ( decimal point can select to DP1, DP2, DP3 ). Until set the display value, all the data will save into the memory circuit permanently | ||
Input Signal | Linear, 4 to 20 mA | |
Accuracy @ 23 ± 5 ℃ | Span | ± ( 0.15% + 2d ) F.S. |
Zero | ± ( 0.1% + 2d ) F.S. | |
* F.S. : full scale | ||
Circuit | Custom chip of microprocessor LSI circuit. | |
Sampling Time | Approx. 1 second. | |
External Power Supply | DC 24 V, 50 mA max. | |
Data Output | RS 232 PC serial interface. | |
Relay Output | Number | 2 relays |
Function | Relay 1 : High/Low control relay. Relay 2 : High/Low alarm relay. | |
Max load | 0.5 ACA/250 ACV 0.5 DCA/24 DCV * Do not apply the relay contact load current > 0.5 A, other wise the relay may be damaged permanently without warranty. | |
Main Internal Function Selection | * Decimal point adjustment : DP1, DP2, DP3 * Low limit of range adjustment 4 mA = X X X X, min. value is -1999 * High limit of range adjustment 20 mA = X X X X, max. value is 9999 * Alarm function adjustment : High Alarm or Low alarm. * Control function adjustment High control or Low control. * Deviation of Alarm * Deviation of Control * Filter value of display reading * Offset adjustment. * Gain adjustment. * RS232 output unit code setting | |
Default of internal function : Without advice previously, the function of CT-2012 will preset : * 4 mA = 0 , 20 mA = 9999. * High control mode. * High alarm mode. * RS232 output unit code = 0 ( no unit ) . | ||
Front Panel Function Selection | * Control set-point value adjustment. * Measuring value ( Process value ) offset. Use to offset the PV indication from the actual PV. * Alarm set-point value adjustment. | |
Operating Temperature | 0 to 50 ℃. | |
Operating Humidity | Less than 80% R.H. | |
Power Supply | 90 to 260 ACV, 50/60 Hz. | |
Power Consumption | Approx. 3.5 VA/AC 110V. Approx. 4.9 VA/AC 220V. | |
Weight | 384 g/ 0.84 LB. | |
Dimension | DIN size : 96 x 48 mm. Panel cut size : 92 mm x 46 mm. Depth : 110 mm. | |
Accessories Included | Instruction manual...........................1 PC Case holder with screw....................2 PCs | |
Optional Accessories | * Data Acquisition software, SW-U801-WIN. * RS232 cable, UPCB-02. * USB cable, USB-01. |