商品介紹未分類RCB-110V RCCB CHECKER

RCB-110V RCCB CHECKER

RCCB CHECKER
Model : RCB-220V, RCB-110V        ISO-9001, CE, IEC1010



FEATURES

 

GENERAL SPECIFICATIONS

Display

3 LEDs for pin assignment of sockets L-N, L-PE, N-PE.

1 LED for tripping current pulse.

(L-Line, N-Neture, PE-Power Earth)

Applications

* Checking the shock-proof plug pin assignment

* Residual Current Circuit Breaker Test

Rated Tripping Current Settings

10 mA, 30 mA, 100 mA, 300 mA and 500 mA.

Test Current Duration

Approx. 140 ms (200 ms, -30%) according to DIN VDE.

Operating Factor

Approx. 10% for 500 mA range, wait approx. 10 sec between each step.

Tested Mains Voltage

Model : RCB-220V

200V to 240V, 50/60 Hz

Model : RCB-110V

100V to 120V, 50/60 Hz

Power Supply

Directly from mains.

Operating Temp.

0 to 50  (32 to 122 ).

Operating Humidity

Less than 80% RH.

Weight

200 g/0.44 LB.

Dimension

180 x 72 x 32 mm (7.1 x 2.8 x1.3 inch).

Accessories Included

Instruction manual................................................1 PC.

Power cable with Plug.......................................... 1 PC.

 

APPLICATIONS

Checking the shock-proof plug pin assignment.



 If the socket is wired correctly, then the diodes "L-N" and "L-PE" are illuminated.

 

Residual Current Circuit Breaker Test

Measuring Procedures :

  1. If "L" and "N" inverted, then may inverse conductors "L" & "N" by using select the "Phase Polarity Switch".
  2. Select desired tripping current by using select the "Tripping Current Switch".
  3. Trigger the RCCB by pressing the "Test Button".